Description
DVC6200 HC Digital Valve Controller | Fisher Fieldvue
DVC6200 HC Digital Valve Controller | Fisher Fieldvue instrument allows for your operation to run closer to setpoint, improving product quality with more accurate control. Using FIELDVUE Performance Diagnostics, valve operation is monitored online to evaluate performance and reliability.
Specification of DVC6200 HC Digital Valve Controller :
Communication Protocol
- HART 5 or
- HART 7
Input Signal
- Point-to-Point
- Analog Input Signal: 4-20 mA DC, nominal; split ranging available
- Minimum Voltage Available at Instrument Terminals
must be 9.5 VDC for analog control, 10 VDC for HART
communication. - Minimum Control Current: 4.0 mA
- Minimum Voltage Available at Instrument Terminals
- Minimum Current w/o Microprocessor Restart: 3.5 mA
- Maximum Voltage: 30 VDC
- Overcurrent protected
Reverse Polarity protected
Multi-drop - Instrument Power: 11 to 30 VDC at 10 mA
- Reverse Polarity protected
Supply Pressure(1)
- Minimum Recommended: 0.3 bar (5 psig) higher than maximum actuator requirements
- Maximum: 10.0 bar (145 psig) or maximum pressure rating of the actuator, whichever is lower
- Medium:Air or Natural Gas
- Supply medium must be clean, dry and noncorrosive.
Output Signal
- Minimum Span: 0.4 bar (6 psig)
- Maximum Span: 9.5 bar (140 psig)
- Action:
Double,
Single Direct or
Reverse
Maximum Output Capacity(2)(3)
- At 1.4 bar (20 psig) supply pressure:
10.0 normal m3/hr (375 scfh) - At 5.5 bar (80 psig) supply pressure:
29.5 normal m3/hr (1100 scfh)
Operating Ambient Temperature Limits(1)(4)
- -40 to 85℃ (-40 to 185℉)
-52 to 85℃ (-62 to 185℉) for instruments utilizing
the Extreme Temperature option (fluorosilicone
elastomers)
-52 to 125℃ (-62 to 257℉) for remote‐mount
feedback unit
Independent Linearity(5)
- Typical Value: ±0.50% of output span
Operating :
- Tested per ANSI/ISA-S75.13.01 Section 5.3.5. A resonant frequency search is performed on all three axes. The instrument is subjected to the ISA specified 1/2 hour endurance test at each major resonance…..more
Input Impedance
- An equivalent impedance of 500 ohms may be used. This value corresponds to 10V @ 20 mA.
Humidity Testing Method
- Tested per IEC 61514‐2
Electrical Classification
- Hazardous Area Approvals
- CSA—Intrinsically Safe, Explosion‐proof,
Division 2, Dust Ignition-proof - FM— Intrinsically Safe, Explosion‐proof,
Dust Ignition-proof, Non-Incendive - ATEX— Intrinsically Safe, Flameproof, Type n
Dust by intrinsic safety - IECEx— Intrinsically Safe, Flameproof, Type n
Dust by intrinsic safety and enclosure - Electrical Housing
- CSA— Type 4X, IP66
- FM— Type 4X, IP66
- ATEX— IP66
- IECEx— IP66
Other Classifications/Certifications
- Natural Gas Certified, Single Seal Device— CSA, FM,
ATEX, and IECEx - Lloyds Register— Marine Type Approval
- CCC— China Compulsory Certification
- CML— Certification Management Limited (Japan)
- CUTR— Customs Union Technical Regulations
(Russia, Kazakhstan and Belarus) - DNV— Marine Type Approval
- ESMA— Emirates Authority for Standardization and
Metrology – ECAS-Ex (UAE) - INMETRO— National Institute of Metrology, Quality,
and Technology (Brazil) - KOSHA— Korean Occupational Safety & Health
Agency (South Korea) - NEPSI— National Supervision and Inspection Centre
for Explosion Protection and Safety of
Instrumentation (China) - PESO CCOE— Petroleum and Explosives Safety
Organisation – Chief Controller of Explosives (India) - SANS— South Africa National Standards
Connections
- Supply Pressure: 1/4 NPT internal and integral pad for
mounting 67CFR regulator - Output Pressure: 1/4 NPT internal
- Tubing: 3/8‐inch recommended
- Vent: 3/8 NPT internal
- Electrical: 1/2 NPT internal or M20
Actuator Compatibility
- Sliding‐Stem Linear
Linear actuators with rated travel between 6.35 mm
(0.25 inch) and 606 mm (23.375 inches) - Quarter‐Turn Rotary
Rotary actuators with rated travel between
45 degrees and 180 degrees(6)
Weight
- DVC6200
Aluminum:3.5 kg (7.7 lbs)
Stainless Steel:8.6 kg (19 lbs) - DVC6205: 4.1 kg (9 lbs)
- DVC6215: 1.4 kg (3.1 lbs)
Construction Materials
- Housing, module base and terminal box:
A03600 low copper aluminum alloy (standard)
Stainless steel (optional) - Cover: Thermoplastic polyester
- Elastomers: Nitrile (standard)
Fluorosilicone (extreme temperature)
Features of DVC6200 HC Digital Valve Controller :
- Supply and output pressure gauges or
- Tire valves
- Integral mounted filter regulator
- Low‐Bleed Relay(7)
- Extreme Temperature
- Remote Mount(8)
- Stainless Steel
- Integral 4‐20 mA Position Transmitter(9):
4‐20 mA output, isolated
Supply Voltage: 8‐30 VDC
Reference Accuracy: 1% of travel span
The position transmitter meets the requirements of
NAMUR NE43; selectable to show failure high
( > 22.5 mA) or failure low (< 3.6 mA). Fail high only
when the positioner is powered. - Integral Switch(9):
One isolated switch, configurable throughout the
calibrated travel range or actuated from a device alert
Off State: 0 mA (nominal)
On State: up to 1 A
Supply Voltage: 30 VDC maximum
Reference Accuracy: 2% of travel span
For complete datasheet : TSP Controls – Fisher DVC6200 AD Datasheet