Sale!

Deltabar S PMD75 | Endress + Hauser

Original price was: $1,500.00.Current price is: $1,100.00.

Description

Deltabar S PMD75 | Endress + Hauser

Differential pressure transmitter with ceramic and mono silicon sensors for flow, level and differential measurement High accuracy with excellent long-term stability HART®, PROFIBUS® PA or FOUNDATION™ Fieldbus protocol

  • Manufacturer : Endress+Hauser
  • Part Number : PMD 75
  • Differential pressure, capacitive.
  • Transmitter.
  • Application: pressure, level, flow.
  • Membrane: ceramic.
  • A- Approval: For non-hazardous areas
  • A- Output; Operation: -4…20 mA HART, SIL operation outside, LCD
  • L -Housing; Cable entry; Protection:Aluminium T15 housing, optional display on the top, IP 66/67/NEMA 6P, Thread 1/2 NPT
  • 7F- Nominal range; PN: 500 mbar/50 kPa/7.5 psiNominal value PN : 100 bar/10 MPa/1500 psi
  • 3-Calibration; Unit: Nominal range; mmH2O/mH2O
  • B-Process connection; Material: 1/4 – 18 NPT IEC 61518, mounting: 7/16 – 20 UNF, C22.8 (CRN)
  • A-Seal:FKM Viton
  • A- Additional option 1: not selected
  • A- Additional option 2: not selected
  • connection Additional Weight : 4.0 kg
  • housing Additional Weight : 1.8 kg
  • Shipping Weight : 8 Kg
  • Origin : Germany

Benefits of Deltabar S PMD70/75 :

• Excellent reproducibility and long-term stability
• High accuracy: up to ±0.075%, (<15:1 turndown), with optional PLATINUM version: ±0.05% span
• Turn down 100:1, higher on request
Designed with safety in mind to keep your plant, equipment and personnel safe:
• Used for flow and differential pressure monitoring up to SIL3, certified to IEC 61508 by TÜV SÜD
• Meets PED (Pressure Equipment Directive)
• Secondary seals standard in every transmitter
• Built-in diagnostic software functionality (e.g. userdefined max. / min. operating window)
• Function-monitored from the measuring cell to the electronics
• Modularity for easy, cost-effective repair – replaceable display
– universal electronics for pressure and differential pressure
• Easy setup with menu-driven interface, quick setup menu for standard application modes including
pressure, level and flow……more

Features and specifications of Deltabar S PMD75 :

  • Measuring principle

    Differential pressure

  • Characteristic

    Digital transmitter with ceramic measuring diapragms
    Modular transmitter
    Long-term stability
    Enhanced safety via self diagnostic functions
    Secondary process barrier

  • Supply voltage

    4…20mA HART:
    10,5…45V DC
    Ex ia: 10,5…30V DC
    PROFIBUS PA /
    FOUNDATION Fieldbus:
    9…32V DC

  • Reference Accuracy

    0,075%
    “PLATINUM” 0,05%

  • Long term stability

    0,05% of URL/year
    0,125% of URL/5 years

  • Process temperature

    -20°C…85°C
    (-4°F…185°F)

  • Ambient temperature

    -20°C…85°C
    (-4°F…185°F)

  • Measuring cell

    25mbar…3bar
    (10inH2O…45psi)

  • Max. overpressure limit

    on one side:
    100 bar
    (1500 psi)

  • Process connection

    1/4-18NPT
    RC1/4″

  • Communication

    4…20mA HART
    PROFIBUS PA
    FOUNDATION Fieldbus

  • Certificates / Approvals

    ATEX
    FM
    CSA
    NEPSI
    IECEx

  • Safety approvals

    SIL
    Overfill prevention WHG ,

Application:

The Deltabar S differential pressure transmitter are
suitable for:
• Flow measurement (volume or mass flow) in conjunction with primary elements in gase, steam and liquids
• Level, volume or mass measurement in liquids • Differential pressure monitoring, e.g. across filters and pumps
• Corrosive or abrasive applications using unique ceramic sensor technology (PMD70). For example, DP
measurement across a filter with abrasive product
• High temperatures up to 662°F (350°C) with remote diaphragm seals (FMD78)

For complete datasheet,  ….TSP Controls- Deltabar PMD75 Datasheet

Deltabar S PMD75 | Endress + Hauser

 

Send Enquiry                                    Buy Now

Reviews

There are no reviews yet.

Be the first to review “Deltabar S PMD75 | Endress + Hauser”

Your email address will not be published. Required fields are marked *